Closed Type Water Cooling

Cooling water shall be free from impurities. DOT NOT use well water or river water. To prevent the scale formation, ensure good cooling result, and greatly reduce the failure rate, Soften Water or Distilled Water are strongly recommended as cooling water for induction equipment.

SKU: 1646 Category:

Technical information

Specification of Water quality:

PH: 7-8.5

Suspended solids<10mg/L

Hardness<60mg/L

Conductivity<500μA/cm3

Chloride ion: Average<60mg/L

Sulfate ion<100mg/L

Iron<2mg/L

Solubilitysio2<6mg/L

Dissolved solid<300mg/L

Feature

Closed-cycle cooling medium and no impurity, ensure the purity of the medium;

The use of DI water ensures non-scaling and non-clog in water pipe.

Small space required, easy to move

Low energy loss, operation is simple and reliable.

Cooling water tank and DI water tank use stainless steel to avoid rusting.

Specification (For 600KW)

 

Model CL-60
Cooling Capacity 300000 kcal/h
Cooling water flow 60 m3/h
Power of Fan 1.5kw x 2
Power Input 380V/50Hz
Wind capacity of fan 22000 m3/h X 2
Power of spray pump 3kw
Water flow of spray pump 50 m3/h
Lift if spray pump 13m
Power of main pump 11kw   (two pumps)one main pump and one spare pump
Water flow of main pump 50 m3/h
Lift of main pump 48m
Water inlet & outlet DN:80
Working pressure 0.1~0.45Mpa
Dimension of cooling tank 2850×1300×2650

 

Closed Type Water Cooling

Closed Type Water Cooling