Technical information
Specification of Water quality:
PH: 7-8.5
Suspended solids<10mg/L
Hardness<60mg/L
Conductivity<500μA/cm³
Chloride ion: Average<60mg/L
Sulfate ion<100mg/L
Iron<2mg/L
Solubilitysio2<6mg/L
Dissolved solid<300mg/L
DI water cooling system | Cooling | Cooling Tower for DI water cooling system (Prepared by customers) | Capacity of water tank | |||
Water flow of pump | Power output of Pump | Lift of pump | Water flow of cooling tower | |||
BKL-250-4.0 | Power unit & Heater | ≥15m3/h | 4KW | ≥22m | ≥10m3/h | ≥5 m3 |
BKL-250-7.5 | Power unit & Heater | ≥25m3/h | 4KW | ≥22m | ≥16m3/h | ≥10 m3 |
Feature
• The use of DI water ensures non-scaling and non-clog in water pipe.
• Stainless steel DI water tank and connector avoid rusting
• Small space required, easy to move
• Low energy loss, operation is simple and reliable.
Specification
Model | BKL-250-4.0 | BKL-400-7.5 |
Cooling capacity | 51600Kcal/h | 155000 Kcal/h |
Water flow | 9-18 m3/h | 20-42 m3/h |
Power of water pump | 4.0KW | 7.5KW |
Water capacity of tank | 250L | 400L |
Outside diameter of outlet cooling water | DN40(Quick coupler) | DN65(Flange) |
Dimension | 1300× 870× 930 (mm) | 1550× 1000× 1050 (mm) |
Noise | ≤70 dB(A) | ≤70 dB(A) |
Ambient temperature | 8~40℃ | 8~40℃ |
Installation (For reference only)
Model | DI water cooling system | Cooling | Cooling Tower for DI water cooling system (Prepared by customers) | Capacity of water tank | |||
Water flow of pump | Power output of Pump | Lift of pump | Water flow of cooling tower | ||||
MFP-100D2 | BKL-250-4.0 | Power unit & Heater | ≥15m3/h | 4KW | ≥22m | ≥10m3/h | ≥5 m3 |
MFP-160D2 | BKL-250-7.5 | Power unit & Heater | ≥25m3/h | 4KW | ≥22m | ≥16m3/h | ≥10 m3 |
MFP-250D2 | BKL-250-4.0 | Power unit | ≥30m3/h | 5.5KW | ≥22m | ≥25m3/h | ≥15 m3 |
BKL-400-7.5 | Heater | ||||||
MFP-350D2 | BKL-400-4.0 | Power unit | ≥40m3/h | 5.5KW | ≥22m | ≥32m3/h | ≥15 m3 |
BKL-400-7.5 | Heater | ||||||
MFP-500D2 | BKL-250-4.0 | Power unit | ≥55m3/h | 7.5KW | ≥22m | ≥45m3/h | ≥20 m3 |
BKL-400-7.5 | Heater | ||||||
MFP-600D2 | BKL-250-4.0 | Power unit | ≥65 m3/h | 9.2KW & 11KW | ≥22m | ≥55m3/h | ≥25 m3 |
BKL-400-7.5 | Heater | ||||||
MFP-750D2 | BKL-250-4.0 | Power unit | ≥80m3/h | 9.2KW & 11KW | ≥22m | ≥70m3/h | ≥30 m3 |